INFORMATION SHEET
/uploads/products/GDA_4360_FRONT2.png/uploads/products/GDA_4360_DIA_2.png

The GDA 4360 is a 3 wire 4-20 mA Non Dispersive Infra red (NDIR) Carbon Dioxide detector. It gives a 4-20 mA o/p over the range of the sensor. Designed for applications where low profile intrusion into a room space is required. The unit fits into a GPO Clipsal spacing using P clamps. It uses laser LED to give reliable performance. Calibration for non critical safety applications is every 3 years. There is a low temperature version (suffix LT) which operates from - 25°C to 45°C.


DESIGNED, MANUFACTURED and SUPPORTED by GAS DETECTION AUSTRALIA.

  • 12 - 32 VDC
  • Clipsal 2000 series enclosure
  • 4-20 mA o/p linear over range of sensor
  • 3 wire 4-20 mA
  • No cross sensitivity to other gas
  • Temperature and humidity compensated
  • No moving parts
  • Factory calibrated
  • Low drift
  • Multiple ranges

DESIGNED, MANUFACTURED and SUPPORTED by GAS DETECTION AUSTRALIA.

Refrigerant Gas: Plant Rooms & Offices

Gas Detection Australia has a range of ultra-low level refrigerant gas leak detection systems specifically developed to prevent the expensive results of refrigerant gas leaks.. R22; R123; R134, R407; R410; Ammonia, Carbon Dioxide; Propane

MEETS THE REQUIREMENTS OF  AS 1677.1 & 2

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Cellar Gas Detection

The ACGS-01 uses the latest patented laser source technology to provide reliable accurate and cost effective solutions for Carbon Dioxide gas detection in cellar gas detection applications. The Carbon dioxide cellar gas detection system  ACGS-01 comprises of a remote  carbon dioxide gas detector / gas sensor, an external  control unit + power supply (to view the gas levels and alarms before entry ) and a audio visual sounder/ flasher that  will activate on alarm. Gas Detection Australia offer a range of solutions to meet individual site requirements for carbon dioxide  cellar gas detection systems  and oxygen  cellar gas detection  when using nitrogen for  pre-mix drinks

MEETS THE REQUIREMENTS OF AS5034-2005.

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Laboratory and Classroom Monitoring

When gas is piped into rooms for experimental purposes such as CO2, CO, or Natural Gas .The Gas Detection Australia range of sensors can be used to detect any leaks that may present a danger to health or explosion.

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Air Conditioning Monitoring

Air conditioning gas detection systems are used in a number of ways. In air conditioning plant rooms  Gas Detection Australia  has  gas sensors and gas detectors  for Ammonia , Propane, CO2 and  R134a, R123, R125, R404, R407c  R410a etc. In enclosed laboratories classrooms and workspaces. The Gas Detection Australia  range of flush mounted Air Conditioning gas sensors for Carbon Dioxide GDA 4360 are used by the HVAC industry  to control fresh air input into rooms and modulate supply. In the case of VRF systems needing room air conditioning gas detection  HVAC industry  uses the flush mounted GDA 3160 which are unobtrusive and used to detect low  levels of R134a, R123, R404, R407c, R410 etc.

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Cryogenic Rooms

Cryogenic freezing using liquid Nitrogen poses a problem of oxygen depletion. The GDA 2528 oxygen gas detector / gas sensor offers a cost effective method of detection and low cost of maintenance. For standalone cyro-storage chambers housed in laboratories , the storage area can be monitored for oxygen depletion by the standalone GD40125 system.

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Cold Rooms

The use of Carbon Dioxide gas detectors / gas sensors or Nitrogen gas detectors / gas sensors in cold rooms can result in asphyxiation if the levels get too high . Work place health and safety places a requirement for monitoring these gases

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Flush Mount Gas Sensors

Mounted in wall hole, Non obtrusive, recommended for office rooms, class rooms, laboratories etc. Are designed to fit into a Clipsal double gang GPO wall mount.

DESIGNED, MANUFACTURED AND SUPPORTED IN AUSTRALIA.

Specification NameSpecification Value
Detectable GasesCarbon Dioxide
Detectable Gas RangesSee Ordering Information
Power Requirements12 - 32 VDC
Output Types4-20 mA
Power Consumption<30 mA @ 24 VDC
Output Specificationsmax loop Impedance 800 Ω @ 24 VDC
Connection4 way plug
Wiring3-wire (0.75mm2) with overall screen
Operating Temperature-25 to +55 °C
Operating Humidity0 to 95% RH (non-condensing)
Accuracy of Reading+- 2% FSD +-0.5% reading @STP
Warm Up Time<30 sec
Response Time<20 sec
Zero Drift<0.5% / FSD for 90days @STP
Calibration Drift<0.5% FSD for 90 days @STP
Sensor TechnologyNon Dispersive Infra-Red (NDIR)
Calibration RequirementAnnually if sensor operated at STP
DimensionsClipsal 2000 series 116 x 76 x 13 mm (L, W, D) in wall depth 40 mm
Enclosure MaterialABS Plastic
Cable Entry Rear
Product Description
4360-01 0-2000ppm Carbon Dioxide detector
4360-01-LT 0-2000ppm Carbon Dioxide detector Low Temperature -25°C to 45°C
4360-02 0-10000ppm (1%vol) Carbon Dioxide detector
4360-02-LT 0-10000ppm (1%vol) Carbon Dioxide Low Temperature detector -25°C to 45°C
4360-03 0-5%vol Carbon Dioxide detector
4360-03-LT 0-5%vol Carbon Dioxide detector Low Temperature -25°C to 45°C
4360-04 0-20%vol Carbon Dioxide detector
4360-04-LT 0-20%vol Carbon Dioxide detector Low Temperature -25°C to 45°C
4360-06 0-100%vol Carbon Dioxide detector
4360-06-LT 0-100%vol Carbon Dioxide detector Low Temperature -25°C to 45°C

 

/uploads/products/4360_IMP01.png